The bridge travelling motor installed at the opposite end from the bridge panel.
The bridge travelling motor installed at the bridge panel end of the main girder.
The frequency converter.
If the European regulations for EMC are not adhered to, both motor cables can be 40 m long.
Exception: 003 with two motors (MF06MA200)
Model 003 with two motors shall be connected as illustrated in the following picture. The grounding cables of the
motors shall be connected to the grounding terminals of the converter. The ferrite component shall be placed on
the wires between the frequency converter and the terminal blocks, near the converter. The phase and grounding
wires shall go through the ferrite component twice.