Power class 002 003 004 005 007 011 015 018 022
Continuous current I
CONT
A 6.5 8 10 13 18 24 32 42 48
Fuse A 10 10 10 16 20 25 35 50 50
Max motor cable length m 50 50 50 50 50 50 50 50 50
Ft 160 160 160 160 160 160 160 160 160
Motor cable 40
C mm
1.5 2.5 2.5 2.5 4 6 10 10 10
104
F AWG 14 14 14 12 10 10 8 8 6
Braking resistor cable 40
C mm
2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4
104
F AWG 14 14 14 14 14 14 14 12 12
Power class 030 037 045 055
Continuous current I
CONT
A 60 75 90 110
Fuse A 63 80 100 125
Max motor cable length m 50 50 75 75
Ft 160 160 240 240
Motor cable 40
C mm
16 25 35 35
104
F AWG 6 4 2 2
Braking resistor cable 40
C mm
10 10 16 16
104
F AWG 8 8 6 6
1.11.4 Cable protection
To protect the supply cables against short circuit there must be fuses or motor circuit breakers (MCCBs) installed at the
mains end of the supply cable. Dimensioning of the fuses or MCCBs depends on the cable used and on the type of
primary fuses or MCCBs. If there are no other regulations, the values given in this section can be used to dimension
fuses (three phase 400V supply).
The overload protection of inverter protects both the supply and the motor cables. The fuses of the supply provide the
short circuit protection.
1.11.5 Cable length
The maximum motor cable lengths in the preceding table are based on 150% of inverter rated current (=current during
acceleration) and a 2.5 % voltage drop in the cable. For longer cables, the required conductor cross sectional area A
(mm2) is given by formula
Up
Il
A
F
×
×=
5.1
43.2
where l is the cable length (m)
I
F
is the motor current (A) at shaft power P
F
p is the allowed voltage drop in %
U is the nominal motor voltage
1.11.6 Du/dt filters
If inverter is not mounted on the crane, there has to be du/dt filter at motor supply. Also if total motor cable length (sum of
motor cables ) is over 100m with 002 –005 or over 200m with 007 –055, there has to be du/dt filter at motor supply.
Power class Platthaus du/dt filter Length (mm) Width (mm) Height (mm) Weight (kg) ID
002 – 003 ULC-910-920 100 110 180 1.2 52306553
004 – 005 ULC-914-931 125 110 200 3 52306554
007 – 018 ULC-918-951 155 125 225 7 52306555
022 – 045 ULC-923-927 190 135 260 12 52306556
055 ULC-942-1044 240 175 310 22 52306557
m Du/dt filter should be as near inverter as possible
m Note! All control cables must be placed as far from the motor and braking resistor
cables as possible.