R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325
-
5319
56/83
R&M Materials Handling, I
undervoltage trip
F 10 Input line
supervision
One input line phase is missing. Check:
supply voltage
mains connection.
X
F 11 Output phase
supervision
Current supervision has sensed that at least
one of the motor phases has no current
Check:
motor cable connections
measure motor phase currents and compare to display
value
X
F 12 Braking
chopper
supervision
Braking chopper or braking resistor circuit
has failed. Test pulse measures transistor
collector voltage. Fault appears if
braking resistor is broken
braking chopper is broken
braking resistor is not installed
Reset: switch power off and restart after the lamps of
display are off.
Check:
braking resistor and insulation resistance
measure braking transistor IGBT and free wheeling
diodes
If resistor is OK, then the chopper is broken
Contact authorized
service
X
F 13 Inverter
undertemperatu
re
Temperature of heat sink is below
acceptable operating level (-10°C /14°F)
Check
ambient temperature
cubicle heating
X
F 14 Inverter
overtemperatur
e
Temperature of heat sink is over acceptable
operating level
+90°C (194°F).
Overtemperature warning is issued when the
heat sink temperature exceeds +85°C (185°F)
Check:
ambient temperature
inverter cooling fan operation
cooling air flow through heat sink
heat sink is not dusty
X
F 22
F 23
EEPROM
checksum fault
Parameter save error
interference fault
component failure (control unit)
After power off the inverter will automatically reset
parameter settings. The drive does not work properly nor
enable driving after this fault.
Check:
all parameter settings.
+24V voltage output loading
If the fault comes again, contact authorized
service
center.
X
F 24 Changed data
warning
Changes may have occurred in the different
counter data due to mains interruption
No special actions required. Take a critical attitude to the
counter data.
X
F 25 Microprocessor
watchdog-fault
interference fault
component failure (control unit)
Reset: switch power off and restart after the lamps of
display are off.
If the fault comes again, contact service.
X
F 26 Power Unit
Fault
X
F 31 IGBT
temperature
Too high temperature in IGBT. A hardware
temperature measurement has tripped.
Reset: switch power off and restart after the lamps of
keypad are off. Check:
motor loading
brake operation
inverter heatsink
inverter cooling fan operation
environment temperature
X
F 32 Fan cooling
fault
Cooling fan of the frequency converter do
not work, when ON command has been
given
If the fault comes again, contact authorized
service. X
F 35 Application
fault
Run-time exception in the application
program
Contact authorized service. X
F 36 Control Unit Faulty Control Unit. Contact authorized service. X
F 37 Device changed
Option board changed. Reset the fault X
F 38 Device added Option board added. Reset the fault X
F 39 Device
removed
Option board removed. Reset the fault X
F 40 Device
unknown
Unknown option board or drive. Check board and drive type. X
F 41 IGBT
tempetature
Too high temperature in IGBT transistors.
long duration overload
lowered cooling
high environment temperature
Reset: switch power off and restart after the lamps of
keypad are off. Check:
motor parameters
u/f curve settings
motor loading
brake operation
inverter heatsink
inverter cooling fan operation
environment temperature
X
F43 Encoder failure
Encoder failure.
Subcodes:
S1 = EA+/- is missing
S2 = EB+/- is missing
Check:
Encoder cabling
Brake opening
Encoder mechanical assembly
X