The drive includes an automatic fault reset operation; the fault code stays on the display until the fault is removed
and the controller released back to 0-position. Some of the fault codes require to switch the power off before run is
possible.
The faults are stored to the fault history, from there they can be seen if necessary. The fault history can store last
30 fault codes. Following exceptions exist when storing faults to the fault history
not stored faults: F6, F70
repeated faults are stored only once: F50, F51, F55, F60, F66, F71, F72
READYSTOP
M8.
Fault History
H1
Hxx
READYSTOP
H8.1.
57 Thermistor
F T1
T13
READYSTOP
Operation days
0
I/O term I/O term I/O term
T8.1.1.
Fault
code
Fault
Possible cause
Checking
A
B
F 1 Overcurrent
Inverter has measured too high current (over
4*In) in the motor output:
sudden heavy load increase
short circuit in the motor or cable
not suitable motor
wrong motor parameters
Reset: switch power off and restart after the lamps of
display are off.
Check:
brake operation
motor type and power rating
parameters
motor cable connection
motor insulation
motor loading
X
F 2 Overvoltage DC-bus voltage has exceeded 135%
maximum level, 911Vdc
supply voltage raised >1.35 x Un (high
overvoltage spikes at mains or not
sinusoidal wave form)
Deceleration time is too short
Reset has an additional 5s time delay.
Check:
Adjust the deceleration time longer
measure main supply voltage level and wave form while
not driving
motor insulation
motor cable insulation (phase-ground, phase-phase)
braking resistor cable
braking resistor type and resistance
braking chopper operation
X
F 3 Earth fault Current measurement has sensed
unbalance in motor phase currents.
Supervision level is 5% of inverter nominal
current
not symmetric load
insulation failure in the motor or the cables
Reset has an additional 5s time delay.
Check:
motor insulation
motor cable insulation (phase-ground, phase-phase)
X
F 5 Charging
switch
Charging switch is open when START
command becomes active
interference fault
component failure
Check:
control unit and power unit connections
charging resistors
If the fault comes again, change the control unit.
X
F 6 External Stop
Either the ES or RDY-signal has been
tripped during run
Fault is not stored into fault history.
Check:
ES and RDY external connections
X
F 7 Saturation trip Very high overload or defective component
Reset: switch power off and restart after the lamps of
display are off.
Check:
motor and motor cable insulation
measure main circuit diodes and IGBT transistors
If the fault comes again, change the power unit.
X
F 8 System fault
System
fault due to component failure or
faulty operation
.
Reset: switch power off and restart after the lamps of
keypad are off.
Check:
read fault extension code and contact authorized service
If the fault comes again, change the D2V.
X
F 9 Undervoltage DC-bus voltage has dropped below 333Vdc
mains supply voltage interrupted
inverter fault can also cause an
undervoltage trip
external fault during run may cause an
In case of temporary supply voltage break, reset the
fault and start again. Check mains input.
If mains supply is correct, an internal failure has occurred.
Contact authorized service.
X